Back to the product
SureSafe Safety & Lifting Solutions Pvt Ltd
PRODUCT DATASHEETDoc. SSLS/DS/GD-002 · Rev. 01 · 13-Oct-2026
Gas detection Brand: Honeywell

705 High Temperature Flammable Gas Sensor

Honeywell 705 High Temperature Flammable Gas Sensor

Overview

The Model 705 high temperature sensor has been specifically designed for the detection of combustible gases in high temperature hazardous area locations. Typical applications include turbine enclosures and drying ovens used insolvent based printing and coating machines.

Key features

  • Certified for hazardous location operation up to +150°C (+302°F)
  • Alarm trip points as low as 5% LEL
  • Fast speed of response
  • Poison resistant detectors
  • Low power consumption

Applications

  • Confined space entry
  • Oil, gas and petrochemical
  • Wastewater and sewage
  • Steel and chemical plants

Standards and certification

Supplier: ISO 9001:2015 certified
SureSafe Safety & Lifting Solutions Pvt. Ltd. · Bengaluru · Mumbai · +91 88804 80495 · sales@suresafesafety.com · suresafesafety.com 1 / 3
SureSafe Safety & Lifting Solutions Pvt Ltd
PRODUCT DATASHEETDoc. SSLS/DS/GD-002 · Rev. 01 · 13-Oct-2026

705 High Temperature Flammable Gas Sensor – technical data

Technical specifications

BrandHoneywell
Alarm Settings5% LEL
Storage LifeUp to 5 years
RepeatabilityBetter than ±2% LEL
Weight rangeCollecting Cone: 175 g / Sample Flow Housing: 110 g / Sensor: 200 g / Weather Protection Housing: 52.4 g
Dimension78 mm x 55 mm (Sensor) / 87 mm x 165 mm dia (Collecting Cone) / Sample Flow Housing: 61 mm x 45 mm x 31 mm / Weather Protection Housing: 76.5 mm x 50.8 mm dia
Humidity RangeContinuous: 20 to 90% RH / Intermittent: 10 to 99% RH
Accuracy0-100% LEL
Maximum Pressure110 kPa
Gas TypeFlammable
Warm Up Time30 min
Stability (zero)With Humidity: < ±3% LEL / With Pressure: < ±3% LEL / With Temperature: < ±3% LEL / With Time: < ±5% LEL/yr
Stability (span)With Humidity: < ±3% LEL / With Pressure: < ±3% LEL / With Temperature: < ±4% LEL / With Time: < ±5% LEL/yr
Speed of ResponseT60 < 6 sec / T90 < 10 sec
Signal OutputmV Bridge
Mounting Thread3/4 in NPT
Measuring Range0-20% LEL, 0-100% LEL (Control Card Dependent)
NEMA RatingNEMA 4X
Power Consumption0.7W @200 mA
Enclosure MaterialAluminum
IndustryEnergy
SureSafe Safety & Lifting Solutions Pvt. Ltd. · Bengaluru · Mumbai · +91 88804 80495 · sales@suresafesafety.com · suresafesafety.com 2 / 3
SureSafe Safety & Lifting Solutions Pvt Ltd
PRODUCT DATASHEETDoc. SSLS/DS/GD-002 · Rev. 01 · 13-Oct-2026

705 High Temperature Flammable Gas Sensor – ordering and care

Ordering information

BrandHoneywell

Inspection and care

Keep sensors and filters clean, charge batteries as directed and record bump tests and calibrations.

Storage

Store in a cool, dry place away from direct sunlight, heat and chemicals.

Data given in good faith from manufacturer information and subject to change without notice. Select PPE based on a site risk assessment. Scan the code for the product page.