Back to the product
SureSafe Safety & Lifting Solutions Pvt Ltd
PRODUCT DATASHEETDoc. SSLS/DS/GD-094 · Rev. 01 · 13-Oct-2026
Gas detection Brand: Honeywell

Sensepoint XCD Gas Detector

Honeywell Sensepoint XCD Gas Detector

Overview

Transmitter provides comprehensive monitoring of combustible, toxic and Oxygen gas hazards in potentially explosive atmospheres - indoors and outdoors.

Key features

  • Flammable (catalytic or infrared), toxic and oxygen versions available
  • Serves new/retrofit, indoor/outdoor applications
  • Stainless steel or aluminum explosion-proof housing options

Applications

  • Confined space entry
  • Oil, gas and petrochemical
  • Wastewater and sewage
  • Steel and chemical plants

Standards and certification

Supplier: ISO 9001:2015 certified
SureSafe Safety & Lifting Solutions Pvt. Ltd. · Bengaluru · Mumbai · +91 88804 80495 · sales@suresafesafety.com · suresafesafety.com 1 / 2
SureSafe Safety & Lifting Solutions Pvt Ltd
PRODUCT DATASHEETDoc. SSLS/DS/GD-094 · Rev. 01 · 13-Oct-2026

Sensepoint XCD Gas Detector – technical data

Technical specifications

BrandHoneywell
Product TypeIndustrial Gas
Relay IncludedYes
Weight range316 Stainless Steel: 11 lbs / Aluminium Alloy LM25: 4.4 lbs
Minimum Temperature-40˚C
Material316 Stainless Steel
Enclosure MaterialEpoxy Painted Aluminium Alloy ADC12 or 316 Stainless Steel
Relay Output Configuration3 x 5A @250 VAC
Number of Relay Outputs3
MountingMounting Plate
Conduit Entries(2) 3/4 in NPT
CommunicationModbus RTU / RS485
Ingress ProtectionIP66
Power ConsumptionCatalytic: 4.9W / Electrochemical Cells: 3.7W / IR: 3.7W
Operating Voltage12 to 32 VDC
IndustryCommercial Buildings / Energy / Manufacturing

Ordering information

BrandHoneywell

Inspection and care

Keep sensors and filters clean, charge batteries as directed and record bump tests and calibrations.

Storage

Store in a cool, dry place away from direct sunlight, heat and chemicals.

Data given in good faith from manufacturer information and subject to change without notice. Select PPE based on a site risk assessment. Scan the code for the product page.